Click to enlarge image
|
Characteristic
- Superior static control terminates static generation protecting sensitive
equipment.
- Lifetime warranty against static generation.
- Perfect for access panel floors as well as direct installations.
- Available in 14 colorways.
- Multiple gauges include 1/8" mm as well as 12" x 12" and
24" x 24" sizes for multiple design requirements.
Conductive & Static-Dissipative Tile
|
Size
|
Thickness
|
|
12" x 12"(304.8mm x 304.8mm)
|
2mm, 1/8"(3.18mm)
|
|
600mm x 600mm
|
2mm, 1/8"(3.18mm)
|
|
24" x 24"(609.6mm x 609.6mm)
|
2mm, 1/8"(3.18mm)
|
|
36" x 36"(914.4mm x 914.4mm)
|
3mm
|
Physical Data
|
ITEM
|
Standard
test method
|
ASTM Spec.
|
Conductive
Tile
|
Static
Dissipative tile
|
|
Electrical/Electrostatic Properties
|
|
Electrical Resistance
|
ESD S 7.1(100W)
|
|
|
|
|
-Surface to Surface
|
NFPA99(500V)
|
2.5 x 104~106
(SD : 106~109)
|
2.5 x 104~106
|
106~108
|
|
|
ASTM F 150(500V)
|
|
-Surface to Graound
|
DIN51969(500V)
|
2.5 x 104~
|
2.5 x 104~
|
Less than 20volts
|
|
Electrostatic Propensity
(=Static Generation)
|
ESD STM 97.2
|
-
|
Less than 20volts
|
Less than 20volts
|
|
Static Decay
|
Federal Test Method
101B Method 4046 at
15% Relative Humidity
|
below 0.5 sec
|
0.01sec
|
0.01sec
|
|
Other Properties
|
|
CEN Classification
|
DIN EN 685
|
|
Class 34+43
|
|
Composition of Material
|
ASTM F 1700,.
Certificate of Compliance
|
|
Homogeneous
|
|
Thickness
|
ASTM F 386
DIN EN428
|
as specified ± 0.005in.
(0.13mm)
|
1/8" /2mm
|
|
Nominal Sizes
|
ASTM F 536
DIN EN427
|
0.016 in./lin.Ft
(0.4mm/304.8mm)
|
12x12" / 24x24" / 36x36"
|
|
Squareness
|
ASTM F 540
|
maximum 0.010 in.
(0.25mm)
|
<0.010"
|
|
Residual Indentation
|
ASTM F1914
DIN EN433
|
average less than 8%
max. single reading 10%
|
<7%
|
|
Flexibility
|
ASTM F 137
|
no crack or break
|
No crack or break
|
|
Dimensional Stability
|
ASTM Fed. Std. No. 501a
Method 6211
DIN EN434
|
<0.020"/ft
(0.51mm/304.8mm)
|
<0.015"/ft
|
|
Resistance to chemicals
|
ASTM F 925
DIN EN423
|
No more than s slight change in surface dulling, surface
attack, or staining
|
|
Resistance to Heat
|
ASTM F 1514
|
 E<8ave,
max
|
<  E=2.0
|
|
Resistance to Light
|
ASTM F 1515
|
 E<8ave,
max
|
<  E=6.0
|
|
Static Load Limit
|
Modified ASTM F970-00
|
-
|
2,500psi
|
|
Smoke Density
|
ASTM E 662
|
<450
|
<450
|
|
Flame Spread
|
ASTM E 84, NFPA 225
|
<75
|
<75
|
|
Fire Resistance
|
DIN 4102
|
|
B1
|
|
|
ONORM B 3810
|
|
B1Q1
|
|
Critical Radiant Flux
|
ASTM E 648, NFPA 253
|
|
>1.08W/cm2(Class Interior Floor Finish, NFPA Life
Safety Code 101)
|
|
Abrasion Resistance
|
ASTM D 1044,
CS-10-F Wheel,
500Gm Weight
|
|
Cycle %Gauge Loss
10,000 1.60
|
|
Resistance to wear
|
DIN EN 660-1
|
|
M
|
|
Effect of Castor Chair
|
DIN EN 425
|
|
No damage
|
|
Color Fastness
|
ISO 105 B02
|
|
At least 6
|
|
Standard for Health care facilities
|
NFPA 99
|
|
Confirms to the requirement of NFPA 99 in effect at
the time of installation
|
|
Fulfils product requirements
|
DIN EN 649
|
|
Yes
|
|
Underwriters Laboratories
|
UL 779
|
|
Meets UL Standard
|

|
|
|
|
| |
|
|
|